1 record (stringin, "$(P)LS331:$(Q):IDN") { |
|
2 field(DTYP, "stream") |
|
3 field(INP, "@LK331.proto getIDN $(PORT)") |
|
4 } |
|
5 |
|
6 record(stringin, "$(P)LS331:$(Q):serial") { |
|
7 field(DTYP, "stream") |
|
8 field(INP, "@LK331.proto getSERIAL $(PORT)") |
|
9 } |
|
10 |
|
11 record(stringin, "$(P)LS331:$(Q):model") { |
|
12 field(DTYP, "stream") |
|
13 field(INP, "@LK331.proto getSERIAL $(PORT)") |
|
14 } |
|
15 |
|
16 |
|
17 grecord(dfanout,"$(P)LS331:$(Q):Init") { |
|
18 field(SCAN,"1 second") |
|
19 field(OUTA,"$(P)LS331:$(Q):Input_sel.PROC PP NMS") |
|
20 field(OUTB,"$(P)LS331:$(Q):Units_sel.PROC PP NMS") |
|
21 field(OUTC,"$(P)LS331:$(Q):HeatRg.PROC PP NMS") |
|
22 field(OUTD,"$(P)LS331:$(Q):Gain_set.PROC PP NMS") |
|
23 field(OUTE,"$(P)LS331:$(Q):Rset_set.PROC PP NMS") |
|
24 field(OUTF,"$(P)LS331:$(Q):Rate_set.PROC PP NMS") |
|
25 field(OUTG,"$(P)LS331:$(Q):RampR_set.PROC PP NMS") |
|
26 field(OUTH,"$(P)LS331:$(Q):InitB.PROC PP NMS") |
|
27 } |
|
28 |
|
29 grecord(dfanout,"$(P)LS331:$(Q):InitB") { |
|
30 field(SCAN,"Passive") |
|
31 field(OUTA,"$(P)LS331:$(Q):Ramp_on.PROC PP NMS") |
|
32 field(OUTB,"$(P)LS331:$(Q):wr_SP.PROC PP NMS") |
|
33 field(OUTC,"$(P)LS331:$(Q):read.PROC PP NMS") |
|
34 field(OUTD,"$(P)LS331:$(Q):readPID.PROC PP NMS") |
|
35 field(OUTE,"$(P)LS331:$(Q):Init.SCAN CA NMS") |
|
36 } |
|
37 |
|
38 record(ao, "$(P)LS331:$(Q):Rset_set") { |
|
39 field(DTYP, "Soft Channel") |
|
40 field(FLNK, "$(P)LS331:$(Q):setRset.VAL PP MS") |
|
41 field(PREC, "0") |
|
42 } |
|
43 |
|
44 record(ao, "$(P)LS331:$(Q):Rate_set") { |
|
45 field(DTYP, "Soft Channel") |
|
46 field(FLNK, "$(P)LS331:$(Q):setRate.VAL PP MS") |
|
47 field(PREC, "0") |
|
48 } |
|
49 |
|
50 record(ao, "$(P)LS331:$(Q):RampR_set") { |
|
51 field(DTYP, "Soft Channel") |
|
52 field(FLNK, "$(P)LS331:$(Q):setRamp.VAL PP MS") |
|
53 field(PREC, "1") |
|
54 } |
|
55 |
|
56 record(ao, "$(P)LS331:$(Q):wr_SP") { |
|
57 field(DTYP, "Soft Channel") |
|
58 field(FLNK, "$(P)LS331:$(Q):SP_scalc.VAL PP MS") |
|
59 field(PREC, "3") |
|
60 } |
|
61 |
|
62 record(ao, "$(P)LS331:$(Q):Gain_set") { |
|
63 field(DTYP, "Soft Channel") |
|
64 field(FLNK, "$(P)LS331:$(Q):setGain.VAL PP MS") |
|
65 field(PREC, "0") |
|
66 } |
|
67 |
|
68 record(mbbi, "$(P)LS331:$(Q):Rg_rdbk") { |
|
69 field(DTYP, "Soft Channel") |
|
70 field(INP, "$(P)LS331:$(Q):Range.VAL NPP MS") |
|
71 field(ZRST, "OFF") |
|
72 field(ONST, "100 mA") |
|
73 field(TWST, "300 mA") |
|
74 field(THST, "1 A") |
|
75 } |
|
76 |
|
77 record(mbbi, "$(P)LS331:$(Q):Ramp_state") { |
|
78 field(DTYP, "Soft Channel") |
|
79 field(INP, "$(P)LS331:$(Q):Ramp_scalc.VAL NPP MS") |
|
80 field(ZRST, "OFF") |
|
81 field(ONST, "ON") |
|
82 } |
|
83 |
|
84 record(mbbo, "$(P)LS331:$(Q):Input_sel") { |
|
85 field(DTYP, "Soft Channel") |
|
86 field(FLNK, "$(P)LS331:$(Q):SetCtl.VAL NPP MS") |
|
87 field(ZRVL, "0") |
|
88 field(ONVL, "1") |
|
89 field(TWVL, "0") |
|
90 field(THVL, "0") |
|
91 field(ZRST, "A") |
|
92 field(ONST, "B") |
|
93 } |
|
94 |
|
95 record(mbbo, "$(P)LS331:$(Q):Units_sel") { |
|
96 field(DTYP, "Soft Channel") |
|
97 field(FLNK, "$(P)LS331:$(Q):SetCtl.VAL NPP MS") |
|
98 field(ZRVL, "1") |
|
99 field(ONVL, "2") |
|
100 field(TWVL, "0") |
|
101 field(THVL, "0") |
|
102 field(ZRST, "K") |
|
103 field(ONST, "C") |
|
104 } |
|
105 |
|
106 record(mbbo, "$(P)LS331:$(Q):HeatRg") { |
|
107 field(DTYP, "Soft Channel") |
|
108 field(FLNK, "$(P)LS331:$(Q):SetHeat.VAL PP MS") |
|
109 field(ZRVL, "0") |
|
110 field(ONVL, "1") |
|
111 field(TWVL, "2") |
|
112 field(THVL, "3") |
|
113 field(FRVL, "0") |
|
114 field(FVVL, "0") |
|
115 field(ZRST, "OFF") |
|
116 field(ONST, "100 mA") |
|
117 field(TWST, "300 mA") |
|
118 field(THST, "1 A") |
|
119 } |
|
120 |
|
121 record(mbbo, "$(P)LS331:$(Q):Ramp_on") { |
|
122 field(DTYP, "Soft Channel") |
|
123 field(FLNK, "$(P)LS331:$(Q):setRamp.PROC PP MS") |
|
124 field(ZRVL, "0") |
|
125 field(ONVL, "1") |
|
126 field(TWVL, "0") |
|
127 field(THVL, "0") |
|
128 field(ZRST, "OFF") |
|
129 field(ONST, "ON") |
|
130 } |
|
131 |
|
132 record(seq, "$(P)LS331:$(Q):readPID") { |
|
133 field(PREC, "1") |
|
134 field(DLY1, ".05") |
|
135 field(LNK1, "$(P)LS331:$(Q):rd_Gain.PROC PP MS") |
|
136 field(DLY2, ".05") |
|
137 field(LNK2, "$(P)LS331:$(Q):rd_Rset.PROC PP MS") |
|
138 field(DLY3, ".05") |
|
139 field(LNK3, "$(P)LS331:$(Q):rd_Rate.PROC PP MS") |
|
140 field(DLY4, ".05") |
|
141 field(LNK4, "$(P)LS331:$(Q):rd_Ramp.PROC PP MS") |
|
142 } |
|
143 |
|
144 record(seq, "$(P)LS331:$(Q):read") { |
|
145 field(PREC, "1") |
|
146 field(DLY1, ".05") |
|
147 field(LNK1, "$(P)LS331:$(Q):readCtl.PROC PP MS") |
|
148 field(DLY2, ".05") |
|
149 field(LNK2, "$(P)LS331:$(Q):rd_rdat_scalc.PROC PP MS") |
|
150 field(DLY3, ".05") |
|
151 field(LNK3, "$(P)LS331:$(Q):rd_SplA_scalc.PROC PP MS") |
|
152 field(DLY4, ".05") |
|
153 field(LNK4, "$(P)LS331:$(Q):rd_SplB_scalc.PROC PP MS") |
|
154 field(DLY5, ".05") |
|
155 field(LNK5, "$(P)LS331:$(Q):rd_Heater.PROC PP MS") |
|
156 field(DLY6, ".05") |
|
157 field(LNK6, "$(P)LS331:$(Q):readSP.PROC PP MS") |
|
158 } |
|
159 |
|
160 record(stringout, "$(P)LS331:$(Q):rd_Rset") { |
|
161 field(DTYP, "Soft Channel") |
|
162 field(FLNK, "0") |
|
163 field(VAL, "RSET?") |
|
164 field(OUT, "$(P)LS331:$(Q):wr_rd_Rset.AOUT PP MS") |
|
165 } |
|
166 |
|
167 record(stringout, "$(P)LS331:$(Q):rd_Rate") { |
|
168 field(DTYP, "Soft Channel") |
|
169 field(FLNK, "0") |
|
170 field(VAL, "RATE?") |
|
171 field(OUT, "$(P)LS331:$(Q):wr_rd_Rate.AOUT PP MS") |
|
172 } |
|
173 |
|
174 record(stringout, "$(P)LS331:$(Q):rd_Ramp") { |
|
175 field(DTYP, "Soft Channel") |
|
176 field(FLNK, "0") |
|
177 field(VAL, "RAMP?") |
|
178 field(OUT, "$(P)LS331:$(Q):wr_rd_Ramp.AOUT PP MS") |
|
179 } |
|
180 |
|
181 record(stringout, "$(P)LS331:$(Q):readSP") { |
|
182 field(DTYP, "Soft Channel") |
|
183 field(FLNK, "0") |
|
184 field(VAL, "SETP?") |
|
185 field(OUT, "$(P)LS331:$(Q):rd_SP.AOUT PP MS") |
|
186 } |
|
187 |
|
188 record(stringout, "$(P)LS331:$(Q):rd_Gain") { |
|
189 field(DTYP, "Soft Channel") |
|
190 field(FLNK, "0") |
|
191 field(VAL, "GAIN?") |
|
192 field(OUT, "$(P)LS331:$(Q):wr_rd_Gain.AOUT PP MS") |
|
193 } |
|
194 |
|
195 record(asyn, "$(P)LS331:$(Q):wr_rd_Rset") { |
|
196 field(FLNK, "$(P)LS331:$(Q):I.VAL PP MS") |
|
197 field(PORT, "$(PORT)") |
|
198 } |
|
199 |
|
200 record(asyn, "$(P)LS331:$(Q):wr_rd_Rate") { |
|
201 field(FLNK, "$(P)LS331:$(Q):D.VAL PP MS") |
|
202 field(PORT, "$(PORT)") |
|
203 } |
|
204 |
|
205 record(asyn, "$(P)LS331:$(Q):wr_rd_Gain") { |
|
206 field(FLNK, "$(P)LS331:$(Q):P.VAL PP MS") |
|
207 field(PORT, "$(PORT)") |
|
208 } |
|
209 |
|
210 record(asyn, "$(P)LS331:$(Q):rd_Ctl") { |
|
211 field(FLNK, "$(P)LS331:$(Q):Control.VAL PP MS") |
|
212 field(PORT, "$(PORT)") |
|
213 } |
|
214 |
|
215 record(asyn, "$(P)LS331:$(Q):rd_CtlParms") { |
|
216 field(FLNK, "$(P)LS331:$(Q):CtlInput.PROC PP MS") |
|
217 field(PORT, "$(PORT)") |
|
218 } |
|
219 |
|
220 record(asyn, "$(P)LS331:$(Q):rd_Heater") { |
|
221 field(FLNK, "$(P)LS331:$(Q):Heater.VAL PP MS") |
|
222 field(PORT, "$(PORT)") |
|
223 field(AOUT, "HTR?") |
|
224 } |
|
225 |
|
226 record(asyn, "$(P)LS331:$(Q):write_SP") { |
|
227 field(PORT, "$(PORT)") |
|
228 } |
|
229 |
|
230 record(asyn, "$(P)LS331:$(Q):rd_SP") { |
|
231 field(FLNK, "$(P)LS331:$(Q):SP.VAL PP MS") |
|
232 field(PORT, "$(PORT)") |
|
233 } |
|
234 |
|
235 record(asyn, "$(P)LS331:$(Q):rd_Spl_a") { |
|
236 field(FLNK, "$(P)LS331:$(Q):SampleA.VAL PP MS") |
|
237 field(PORT, "$(PORT)") |
|
238 } |
|
239 |
|
240 record(asyn, "$(P)LS331:$(Q):rd_Spl_b") { |
|
241 field(FLNK, "$(P)LS331:$(Q):SampleB.VAL PP MS") |
|
242 field(PORT, "$(PORT)") |
|
243 } |
|
244 |
|
245 record(asyn, "$(P)LS331:$(Q):wr_rd_Htr") { |
|
246 field(FLNK, "$(P)LS331:$(Q):Range.VAL PP MS") |
|
247 field(PORT, "$(PORT)") |
|
248 } |
|
249 |
|
250 record(asyn, "$(P)LS331:$(Q):wr_rd_Ramp") { |
|
251 field(FLNK, "$(P)LS331:$(Q):Ramp_scalc.VAL PP MS") |
|
252 field(PORT, "$(PORT)") |
|
253 } |
|
254 |
|
255 record(scalcout, "$(P)LS331:$(Q):setRset") { |
|
256 field(DESC, "Format string for PID input") |
|
257 field(CALC, "$P('RSET %d;RSET?',A)") |
|
258 field(INPA, "$(P)LS331:$(Q):Rset_set.VAL NPP MS") |
|
259 field(OUT, "$(P)LS331:$(Q):wr_rd_Rset.AOUT PP MS") |
|
260 field(PREC, "1") |
|
261 } |
|
262 |
|
263 record(scalcout, "$(P)LS331:$(Q):setRate") { |
|
264 field(DESC, "Format string for PID input") |
|
265 field(CALC, "$P('RATE %d;RATE?',A)") |
|
266 field(INPA, "$(P)LS331:$(Q):Rate_set.VAL NPP MS") |
|
267 field(OUT, "$(P)LS331:$(Q):wr_rd_Rate.AOUT PP MS") |
|
268 field(PREC, "1") |
|
269 } |
|
270 |
|
271 record(scalcout, "$(P)LS331:$(Q):setGain") { |
|
272 field(DESC, "Format string for PID input") |
|
273 field(CALC, "$P('GAIN %d;GAIN?',A)") |
|
274 field(INPA, "$(P)LS331:$(Q):Gain_set.VAL NPP MS") |
|
275 field(OUT, "$(P)LS331:$(Q):wr_rd_Gain.AOUT PP MS") |
|
276 field(PREC, "1") |
|
277 } |
|
278 |
|
279 record(scalcout, "$(P)LS331:$(Q):Ramp_scalc") { |
|
280 field(FLNK, "$(P)LS331:$(Q):RampR.PROC PP MS") |
|
281 field(CALC, "INT(AA)") |
|
282 field(INAA, "$(P)LS331:$(Q):wr_rd_Ramp.AINP NPP MS") |
|
283 field(PREC, "1") |
|
284 } |
|
285 record(scalcout, "$(P)LS331:$(Q):RampR") { |
|
286 field(FLNK, "$(P)LS331:$(Q):Ramp_state.PROC PP MS") |
|
287 field(CALC, "SSCANF(AA,'%s')[2,10]") |
|
288 field(INAA, "$(P)LS331:$(Q):wr_rd_Ramp.AINP NPP MS") |
|
289 field(PREC, "1") |
|
290 } |
|
291 |
|
292 record(scalcout, "$(P)LS331:$(Q):P") { |
|
293 field(CALC, "INT(AA)") |
|
294 field(INAA, "$(P)LS331:$(Q):wr_rd_Gain.AINP NPP MS") |
|
295 field(PREC, "0") |
|
296 } |
|
297 |
|
298 record(scalcout, "$(P)LS331:$(Q):I") { |
|
299 field(CALC, "INT(AA)") |
|
300 field(INAA, "$(P)LS331:$(Q):wr_rd_Rset.AINP NPP MS") |
|
301 field(PREC, "0") |
|
302 } |
|
303 |
|
304 record(scalcout, "$(P)LS331:$(Q):D") { |
|
305 field(CALC, "INT(AA)") |
|
306 field(INAA, "$(P)LS331:$(Q):wr_rd_Rate.AINP NPP MS") |
|
307 field(PREC, "0") |
|
308 } |
|
309 |
|
310 record(scalcout, "$(P)LS331:$(Q):Control") { |
|
311 field(DESC, "Format string for Ctl query") |
|
312 field(CALC, "DBL(AA)") |
|
313 field(INAA, "$(P)LS331:$(Q):rd_Ctl.AINP NPP MS") |
|
314 field(INEE, "0") |
|
315 field(PREC, "3") |
|
316 } |
|
317 |
|
318 record(scalcout, "$(P)LS331:$(Q):Heater") { |
|
319 field(DESC, "Format string for Ctl query") |
|
320 field(CALC, "DBL(AA)") |
|
321 field(INAA, "$(P)LS331:$(Q):rd_Heater.AINP NPP MS") |
|
322 field(INEE, "0") |
|
323 field(PREC, "0") |
|
324 } |
|
325 |
|
326 record(scalcout, "$(P)LS331:$(Q):Range") { |
|
327 field(DESC, "Format string for Ctl query") |
|
328 field(FLNK, "$(P)LS331:$(Q):Rg_rdbk.PROC PP MS") |
|
329 field(CALC, "INT(AA)") |
|
330 field(INAA, "$(P)LS331:$(Q):wr_rd_Htr.AINP NPP MS") |
|
331 field(INEE, "0") |
|
332 field(PREC, "2") |
|
333 } |
|
334 |
|
335 record(scalcout, "$(P)LS331:$(Q):SP") { |
|
336 field(DESC, "Format string for Ctl query") |
|
337 field(CALC, "DBL(AA)") |
|
338 field(INAA, "$(P)LS331:$(Q):rd_SP.AINP NPP MS") |
|
339 field(INEE, "0") |
|
340 field(PREC, "3") |
|
341 } |
|
342 |
|
343 record(scalcout, "$(P)LS331:$(Q):SP_scalc") { |
|
344 field(DESC, "Format string for Ctl query") |
|
345 field(FLNK, "$(P)LS331:$(Q):readSP.PROC PP MS") |
|
346 field(CALC, "$P('SETP 1,%6.3f',A)") |
|
347 field(INPA, "$(P)LS331:$(Q):wr_SP.VAL NPP MS") |
|
348 field(INEE, "0") |
|
349 field(OUT, "$(P)LS331:$(Q):write_SP.AOUT PP MS") |
|
350 field(PREC, "3") |
|
351 } |
|
352 |
|
353 record(scalcout, "$(P)LS331:$(Q):SampleA") { |
|
354 field(DESC, "Convt str fror SplA query") |
|
355 field(CALC, "DBL(AA)") |
|
356 field(INAA, "$(P)LS331:$(Q):rd_Spl_a.AINP PP MS") |
|
357 field(INEE, "0") |
|
358 field(PREC, "3") |
|
359 } |
|
360 |
|
361 record(scalcout, "$(P)LS331:$(Q):SampleB") { |
|
362 field(DESC, "Convrt str from SplB query") |
|
363 field(CALC, "DBL(AA)") |
|
364 field(INAA, "$(P)LS331:$(Q):rd_Spl_b.AINP PP MS") |
|
365 field(INEE, "0") |
|
366 field(PREC, "3") |
|
367 } |
|
368 |
|
369 record(scalcout, "$(P)LS331:$(Q):CtlInput") { |
|
370 field(DESC, "Parse string for Ctl Input") |
|
371 field(FLNK, "$(P)LS331:$(Q):CtlUnits.PROC PP MS") |
|
372 field(CALC, "SSCANF(AA,'%s')[0,0]") |
|
373 field(INAA, "$(P)LS331:$(Q):rd_CtlParms.AINP NPP MS") |
|
374 field(PREC, "1") |
|
375 field(AA, "A") |
|
376 } |
|
377 |
|
378 record(scalcout, "$(P)LS331:$(Q):CtlUnits") { |
|
379 field(DESC, "Parse string for Ctl Unit") |
|
380 field(FLNK, "$(P)LS331:$(Q):CtlUnits_str.PROC PP MS") |
|
381 field(CALC, "INT(SSCANF(AA,'%s')[2,2])") |
|
382 field(INAA, "$(P)LS331:$(Q):rd_CtlParms.AINP NPP MS") |
|
383 field(PREC, "1") |
|
384 field(AA, "A,2") |
|
385 } |
|
386 |
|
387 record(scalcout, "$(P)LS331:$(Q):CtlUnits_str") { |
|
388 field(DESC, "Make Ctl Input string") |
|
389 field(CALC, "A=1?BB:CC") |
|
390 field(INPA, "$(P)LS331:$(Q):CtlUnits.VAL NPP MS") |
|
391 field(PREC, "1") |
|
392 field(A, "1") |
|
393 field(BB, "K") |
|
394 field(CC, "C") |
|
395 } |
|
396 |
|
397 record(scalcout, "$(P)LS331:$(Q):SetCtl") { |
|
398 field(DESC, "Format string for Ctl Set") |
|
399 field(FLNK, "$(P)LS331:$(Q):read.PROC PP MS") |
|
400 field(CALC, "AA+(B?FF:EE)+','+STR(C)[0,0]+DD") |
|
401 field(INAA, "") |
|
402 field(INBB, "$(P)LS331:$(Q):Input_sel.VAL PP MS") |
|
403 field(INPB, "$(P)LS331:$(Q):Input_sel.VAL PP MS") |
|
404 field(INPC, "$(P)LS331:$(Q):Units_sel.RVAL PP MS") |
|
405 field(INDD, "") |
|
406 field(OUT, "$(P)LS331:$(Q):rd_CtlParms.AOUT PP MS") |
|
407 field(PREC, "1") |
|
408 field(AA, "CSET 1,") |
|
409 field(BB, "A") |
|
410 field(B, "0") |
|
411 field(C, "1") |
|
412 field(DD, ",0,1;CSET?") |
|
413 field(EE, "A") |
|
414 field(FF, "B") |
|
415 } |
|
416 |
|
417 record(scalcout, "$(P)LS331:$(Q):readCtl") { |
|
418 field(DESC, "Format string for Ctl query") |
|
419 field(CALC, "AA") |
|
420 field(INAA, "0") |
|
421 field(OUT, "$(P)LS331:$(Q):rd_CtlParms.AOUT PP MS") |
|
422 field(PREC, "1") |
|
423 field(AA, "CSET?") |
|
424 } |
|
425 |
|
426 record(scalcout, "$(P)LS331:$(Q):SetHeat") { |
|
427 field(CALC, "AA+BB+CC") |
|
428 field(INAA, "0") |
|
429 field(INBB, "$(P)LS331:$(Q):HeatRg.RVAL NPP MS") |
|
430 field(OUT, "$(P)LS331:$(Q):wr_rd_Htr.AOUT PP MS") |
|
431 field(PREC, "1") |
|
432 field(AA, "RANGE ") |
|
433 field(BB, "0") |
|
434 field(CC, ";RANGE?") |
|
435 } |
|
436 |
|
437 record(scalcout, "$(P)LS331:$(Q):rd_SplA_scalc") { |
|
438 field(DESC, "Format str for A query") |
|
439 field(CALC, "AA+BB") |
|
440 field(INAA, "$(P)LS331:$(Q):CtlUnits_str.SVAL PP MS") |
|
441 field(INBB, "0") |
|
442 field(OUT, "$(P)LS331:$(Q):rd_Spl_a.AOUT PP MS") |
|
443 field(PREC, "1") |
|
444 field(AA, "K") |
|
445 field(BB, "RDG? A") |
|
446 } |
|
447 |
|
448 record(scalcout, "$(P)LS331:$(Q):rd_SplB_scalc") { |
|
449 field(DESC, "Format str for B query") |
|
450 field(CALC, "AA+BB") |
|
451 field(INAA, "$(P)LS331:$(Q):CtlUnits_str.SVAL PP MS") |
|
452 field(INBB, "0") |
|
453 field(OUT, "$(P)LS331:$(Q):rd_Spl_b.AOUT PP MS") |
|
454 field(PREC, "1") |
|
455 field(AA, "K") |
|
456 field(BB, "RDG? B") |
|
457 } |
|
458 |
|
459 record(scalcout, "$(P)LS331:$(Q):rd_rdat_scalc") { |
|
460 field(DESC, "Format str for rd query") |
|
461 field(CALC, "A=2?EE+BB+CC:DD+BB+CC") |
|
462 field(INPA, "$(P)LS331:$(Q):CtlUnits.VAL NPP MS") |
|
463 field(INBB, "0") |
|
464 field(INCC, "$(P)LS331:$(Q):CtlInput.SVAL NPP MS") |
|
465 field(INDD, "0") |
|
466 field(INEE, "0") |
|
467 field(OUT, "$(P)LS331:$(Q):rd_Ctl.AOUT PP MS") |
|
468 field(PREC, "1") |
|
469 field(A, "1") |
|
470 field(BB, "RDG? ") |
|
471 field(DD, "K") |
|
472 field(EE, "C") |
|
473 } |
|
474 |
|
475 record(scalcout, "$(P)LS331:$(Q):setRamp") { |
|
476 field(DESC, "Format string for PID input") |
|
477 field(CALC, "AA+$P('%d',A)+','+$P('%5.1f',B)+BB") |
|
478 field(INPA, "$(P)LS331:$(Q):Ramp_on.RVAL NPP MS") |
|
479 field(INPB, "$(P)LS331:$(Q):RampR_set.VAL NPP MS") |
|
480 field(OUT, "$(P)LS331:$(Q):wr_rd_Ramp.AOUT PP MS") |
|
481 field(PREC, "1") |
|
482 field(AA, "RAMP 1,") |
|
483 field(BB, ";RAMP?") |
|
484 field(CC, "0") |
|
485 } |
|
486 |
|
487 |