pg9520/db/pg9520.db
changeset 2 c68ad80babeb
parent 1 0ba93e52269a
child 5 069837c56788
equal deleted inserted replaced
1:0ba93e52269a 2:c68ad80babeb
   138     field(ZRVL, "0")
   138     field(ZRVL, "0")
   139     field(ONST, "Active high")
   139     field(ONST, "Active high")
   140     field(ONVL, "1")
   140     field(ONVL, "1")
   141 }
   141 }
   142 
   142 
       
   143 record(mbbo, "$(P)$(R)GateEdge") {
       
   144     field(DESC, "Select which edge to use")
       
   145     field(DTYP, "stream")
       
   146     field(OUT,  "@pg9520.proto setGateEdge $(BUS)")
       
   147     field(ZRST, "Rising")
       
   148     field(ZRVL, "0")
       
   149     field(ONST, "Falling")
       
   150     field(ONVL, "1")
       
   151 }
       
   152 
   143 record(ao, "$(P)$(R)GateLevel") {
   153 record(ao, "$(P)$(R)GateLevel") {
   144     field(DESC, "Sets the gate threshold")
   154     field(DESC, "Sets the gate threshold")
   145     field(DTYP, "stream")
   155     field(DTYP, "stream")
   146     field(OUT,  "@pg9520.proto setGateLevel $(BUS)")
   156     field(OUT,  "@pg9520.proto setGateLevel $(BUS)")
       
   157     field(PREC, "3")
       
   158     field(DRVL, "0.2")
       
   159     field(DRVH, "15")
       
   160     field(EGU,  "V")
       
   161 }
       
   162 
       
   163 record(mbbo, "$(P)$(R)TriggerMode") {
       
   164     field(DESC, "Sets Global Trigger Mode")
       
   165     field(DTYP, "stream")
       
   166     field(OUT,  "@pg9520.proto setTriggerMode $(BUS)")
       
   167     field(ZRST, "Disable")
       
   168     field(ZRVL, "0")
       
   169     field(ONST, "Trigger")
       
   170     field(ONVL, "1")
       
   171 }
       
   172 
       
   173 record(mbbo, "$(P)$(R)TriggerEdge") {
       
   174     field(DESC, "Select which edge to trigger")
       
   175     field(DTYP, "stream")
       
   176     field(OUT,  "@pg9520.proto setTriggerEdge $(BUS)")
       
   177     field(ZRST, "Rising")
       
   178     field(ZRVL, "0")
       
   179     field(ONST, "Falling")
       
   180     field(ONVL, "1")
       
   181 }
       
   182 
       
   183 record(ao, "$(P)$(R)TriggerLevel") {
       
   184     field(DESC, "Sets the trigger threshold")
       
   185     field(DTYP, "stream")
       
   186     field(OUT,  "@pg9520.proto setTriggerLevel $(BUS)")
   147     field(PREC, "3")
   187     field(PREC, "3")
   148     field(DRVL, "0.2")
   188     field(DRVL, "0.2")
   149     field(DRVH, "15")
   189     field(DRVH, "15")
   150     field(EGU,  "V")
   190     field(EGU,  "V")
   151 }
   191 }